Skip to content
Free · no signup · local calculationsCoreless 4:3 winding estimate

Axial flux generator coil design: turns, geometry & loaded voltage worksheet

Compare turns, copper area and speed against estimated loaded voltage, copper loss and coil packing. Start with an illustrative preset, then export your inputs and results for review.

Open coil design calculator

CustomAxialFlux engineering editorial · Created · Reviewed . Preliminary sizing only; hardware performance requires project-specific validation.

Axial Flux Generator Coil Geometry & Loaded-Voltage Calculator

Trade coil turn count, wire gauge, and mean turn length against loaded voltage sag and stator thermal current density. Select an application preset or input custom dimensions below. All fields are required. Calculations update instantly on this device; no server or AI processing is used.

Estimate ready: 496.5 V DC average, 7.45 kW. Current-density screen: WARNING. View results and next steps
Representative Application Presets:
1. Stator & Magnet Geometry
Active envelope outer rim (50 to 1200 mm)
20 mm minimum; ID < OD; radial span ≥ 10 mm
0.2–1.4 T assumed effective air-gap field; not magnet remanence
4–64 even poles; supported pole:coil ratio is 4:3
0.40–0.95 assumed effective pole coverage
2. Coil & Conductor Parameters
3–72 coils, multiple of 3; use 3 coils per 4 poles
1–1000 integer turns per coil
AC loss factors are illustrative; validate strand construction and field losses
0.05–50 mm² net copper per turn; aggregate area of all strands, excluding enamel
Total strands per turn, not parallel phase branches. For strip, use 1.
0.01–10 mm; area = strands × πd²/4 (±5%). Ignored for rectangular strip.
Must divide Q / 3 equally; verify phase/polarity grouping
1–50 mm; rotor gap must also allow insulation and clearances
2–100 mm bundle width; both limbs must fit inside inner coil pitch
3. Operating Point & Duty
10–25,000 RPM; frequency is pole pairs × RPM / 60
0–1000 A: line RMS in AC mode; continuous DC in bridge mode
−20 to 220 °C for resistance correction only; not a predicted temperature
DC bridge model supports star/wye only; delta is available in AC mode
DC: star/wye continuous-current approximation; excludes capacitor-input and battery-clamped loads
0–3 V; bridge subtracts two drops. Ignored for AC.

Current design results

Preliminary estimates only. Current density does not predict temperature or establish safe duty. AC loss and inductance need calibration; output excludes core, magnet, mechanical and no-load field losses.

!
Current-Density Screen: WARNING — Elevated current density (> 6.5 A/mm²). Review copper area, duty and cooling; this tool cannot predict temperature.
Loaded Terminal Voltage
496.5 V
DC average · Sag: 5.7% (Reference: 526.6 V)
Estimated Electrical Output
7.45 kW
Output / (output + copper loss), not shaft efficiency: 96.5%
Current Density (J)
7.42 A/mm²
Illustrative review bands only; validate cooling and hotspots
Total Copper Loss (I²R)
273 W
Phase RMS current: 12.25 A · winding heat estimate
Phase Resistance @ 80°C
0.606 Ω
AC factor k_ac: 1.00 (DC: 0.606 Ω)
Coil Window Fill Factor
51.8%
Packing screen only; dry-wind and check insulation / tooling
Mean Turn Length (L_turn)
244.4 mm
Active leg L_act: 60.0 mm
Total Stator Copper Mass
2.08 kg
0.173 kg/coil × 12 coils
Voltage and Current-Density Screens (Live Render)
Voltage Regulation Envelope:Same-Mode Reference (526.6 V):100% (No Load)Loaded Terminal Voltage (496.5 V):94.3% (Sag: 5.7%)• Phase diagnostic (I_rms · R): 7.4 V• Phase diagnostic (I_rms · X): 10.23 V• Electrical Frequency: 200.0 Hz @ 1500 RPMIllustrative Current-Density Screen:≤ 4.5 (Lower)4.5–10 (Review)> 10 (High)7.4 A/mm²Coil Packing Factor: 51.8%Window Area: 153.0 mm² | Net Cu: 79.2 mm²
Request a drawing review with this design

Your current inputs and estimates are included below. Nothing is sent until you submit the form.

Optional drawings & NDA

Files are delivered directly to our private engineering mailbox. No public download link is created. Review the drawing and NDA process.

For confidential drawings, complete the NDA with our team before uploading. An NDA request or template upload does not execute an agreement. Ask us by email if you need a different secure transfer method.

Email directly

If the form is unavailable, contact [email protected].

How to use the coil design worksheet

  1. Select a preset or enter the stator envelope, 4:3 pole/coil combination, turns and net copper area. All fields are required; defaults are illustrative assumptions.
  2. Enter measured or simulated effective pole flux density and pole coverage. Magnet remanence is not the air-gap field. This tool does not solve the magnetic circuit.
  3. Choose AC for balanced unity-power-factor line RMS current, or star/wye DC for continuous bridge output current. Adjust speed and current; results update locally and immediately.
  4. Review sag, loss and packing warnings. Export the current worksheet and request a drawing review before choosing wire, insulation or tooling.

Calculation basis and limits

Scope: equally spaced, non-overlapping coreless coils with 4 poles per 3 coils, balanced phase assignment and equal parallel paths. Slotted stators and arbitrary winding layouts need a separate model.

No thermal certification: operating temperature is your input for resistance correction. Current-density bands (4.5, 6.5 and 10 A/mm²) and the 65% packing screen are illustrative review triggers, not universal operating limits.

  • Active radial length = (OD − ID) / 2. Mean turn length = 2 × radial length + 1.08 × (inner arc + outer arc). The 8% bend allowance is assumed; replace it with actual wire-path measurements during design review.
  • Fill = turns × bare copper area / (axial thickness × limb width). Enamel, leads, bend radii and voids are excluded. Copper mass uses 8960 kg/m³.
  • R20 = ρ × total phase wire length / area, with ρ = 1.7241 × 10⁻⁸ Ω·m; RT = R20 × [1 + 0.00393 × (T − 20)]. Equal parallel branches reduce resistance by the square of branch count for fixed coil count.
  • Frequency = pole pairs × RPM / 60. Phase EMF = √2π × frequency × series turns × winding factor × effective flux per pole. For the supported ideal 4:3 layout, winding factor = √3 / 2. Pole flux is approximated as coverage × effective field × annular area / poles; waveform harmonics are excluded.
  • Inductance is an isolated-loop geometry approximation, excluding mutual coupling and rotor effects. AC resistance multipliers are uncalibrated sensitivity heuristics capped at 3.5, not a bound on real losses. Compare conductor options using field analysis and supplier strand data.
  • AC: Vphase = max(0, √max(0, Ephase² − (Iphase X)²) − Iphase R). P = √3 × Vline × Iline at unity PF. Delta uses Iphase = Iline / √3 and excludes circulating harmonic current.
  • DC (star only): Vdc ≈ max(0, (3√2/π) × Eline − 2Vdiode − 2R × Idc − (3/π) × X × Idc). Line RMS current ≈ √(2/3) × Idc. This continuous-current approximation excludes capacitor-input charging, battery voltage clamping and large overlap. At zero current, the displayed average is an idealized reference, not an open-circuit capacitor voltage.
  • Copper loss = 3 × Iphase² × Reffective. The displayed output/(output + copper loss) ratio excludes diode, core, magnet, mechanical and other losses. It is not generator shaft efficiency. No-load magnetic-field eddy losses are also excluded.

Illustrative examples from the same model

These are input demonstrations, not tested generators or rated-power claims. Values below are calculated by the same function as the live tool. Load each preset to inspect its complete inputs and warnings.

Calculated examples · model revision 2026-11-03
ExampleSpeed / frequencyVoltage / output estimateCopper loss / current density
Low-speed wind · illustrative inputs320 RPM / 64 Hz138.1 V DC average / 7.18 kW1748 W / 12.87 A/mm² · CRITICAL
High-speed APU · illustrative inputs4200 RPM / 560 Hz423.3 V DC average / 17.78 kW996 W / 24.32 A/mm² · CRITICAL
Micro-hydro · illustrative inputs1200 RPM / 120 Hz177.0 V AC line RMS / 1.16 kW37 W / 3.65 A/mm² · LOWER
Axial flux generator coil design worksheet baseline software result: loaded voltage, copper loss and packing estimates
Actual worksheet execution captured 2026-11-03 using Reset to Baseline: OD/ID 280/160 mm, 16 poles/12 coils, 48 turns/coil, 1.65 mm² round copper, one branch, 8.5 × 18 mm window, effective field 0.82 T, coverage 0.72, 1500 RPM, 15 A continuous DC, 80°C, star bridge and 1.1 V/diode. Site header and floating contact control are hidden in this isolated result capture. This demonstrates software reproducibility, not a physical generator test, customer endorsement or thermal qualification.

Interpret the trade-off before choosing wire

At fixed conductor area, more turns increase both EMF and resistance. At fixed window and fill, doubling turns requires roughly half the copper area and gives about four times the DC resistance. Compare at the required voltage and power, rather than holding current constant unintentionally.

A lower current density does not establish a safe hotspot temperature. Cooling path, ambient temperature, resin conductivity, contact resistance, duty and insulation class require a thermal model and prototype measurements. Litz can reduce skin and proximity losses, but there is no universal frequency at which it becomes mandatory.

If output collapses to zero or sag becomes large, reduce current and check the electromagnetic and load models. The worksheet imposes your current demand; it does not solve a turbine torque curve, battery charging controller or self-consistent operating point.

Compare turns and wire area in the worksheet

Drawing review and prototype hold points

  • Provide coil wire path, pole polarity and phase/polarity map, equal parallel grouping, rotor spacing and mechanical datum drawing.
  • Agree conductor dimensions, enamel build, bend radius and winding tension with the wire supplier; dry-wind a sample before accepting packing.
  • Measure cold/hot resistance, inductance, phase balance and speed–EMF; validate the rectifier with the actual load and cooling boundary.
  • Agree insulation tests, resin compatibility, dimensional acceptance and temperature limits for the specific program before potting. No fixed test voltage or tolerance is prescribed here.

Generator coil design questions

How does turn count affect generator loaded voltage vs open-circuit voltage?

EMF scales with turns for fixed field and speed. At fixed copper window and fill, doubling turns roughly halves conductor area and quadruples resistance. Compare voltage and power at the intended load; resistance does not scale quadratically if conductor area stays fixed.

Can I use aluminum wire in this worksheet?

No. The model uses copper resistivity, temperature coefficient and density. Aluminum needs a separate material model and a review of area, terminations and manufacturing limits.

Which winding layouts are supported?

Only an ideal equally spaced coreless 4:3 pole-to-coil layout with balanced phase assignment. Parallel branches must divide the coils per phase equally. Other layouts need winding and field analysis.

When should a generator coil use Litz wire?

When strand construction, electrical frequency and the local magnetic field make it useful. There is no universal switching frequency. The worksheet uses illustrative AC multipliers; validate loss with field analysis and supplier data.

What is the optimum inner-to-outer diameter ratio?

There is no universal optimum across clearance, thermal, magnetic and manufacturing constraints. Compare actual wire length and packing, then validate the full machine model. The tool does not optimize torque or magnet geometry.

What is a realistic coil packing fill factor?

It depends on conductor shape, enamel, serving, tooling and winding process. This tool flags fill above an illustrative 65% and rejects 100% or more. A lower fill is not a manufacturability guarantee; dry-wind and measure a sample.

Does a lower current-density result mean the coil is safe?

No. Current density does not determine hotspot temperature by itself. Cooling path, ambient, duty, resin, insulation and local field losses require thermal analysis and prototype measurements.

Does this worksheet replace FEA or solve battery charging?

No. It estimates geometry, copper loss and a simplified load envelope. DC assumes a star six-pulse bridge with continuous current, excluding capacitor-input and battery-clamped behavior. Confirm with a circuit/field model and hardware before release.

WhatsApp